62 ATS Designers Guide
Table 4-7 Passage and elevator addressing in the ATS system.
Door number
Elevator
number
DGP
address
Remarks
1-16 None 16
The RAS stations of the control panel –
unidirectional door control
17-20 17-20 1
21-24 21-24 2
25-28 25-28 3
29-32 29-32 4
33-36 33-36 5
37-40 37-40 6
41-44 41-44 7
45-48 45-48 8
49-52 49-52 9
53-56 53-56 10
57-60 57-60 11
61-64 61-64 12
ATS1250/60 Access control DGP:
Bi-directional door control,
Advanced access control functions
4.4.1 Basic Access Control in the Control Panel
The control panel has 16 RAS stations, of which every one can be used for unidirectional
door control. Each RAS station is equipped with an exit button input, and a lock control
output. The load of the outputs is limited to 50mA, so additional controlling equipment
needs to be used. For that, the use of the ATS1340 connection box is recommended. It
contains the appropriate connections to the system bus, power, RAS station, exit button,
and executing devices. The control panel is not suited for powering the executing
equipment (for example. electromagnetic locks), so the proper power supply needs to be
included during the design phase.
The doors controlled by the RAS station can be monitored constantly by the alarm
system, thanks to the programming option of suspending (shunting) the door zone. The
access control system uses the same PIN codes, and the same devices as the alarm
system. At the same time the access control devices can be used to control the alarm
system. In particular, the card readers can use its user counting functions to change its
state. Arming the system, for example, can be performed after the user uses the card
three times while exiting.